ChekVolt voltage ind./test point 2p+earth DC 3000VDC CATIII/IV IP66 HL

GTR-3MT-VI-3K/10-DC3-KITH

Increase personal safety, install ChekVolt voltage indicator/voltage test point. ChekVolt allows you to test absence of voltage without open the enclosure door. Built-in voltage divide 10:1 enabling the use of a standard voltmeter .Avoid arc flash hazards, work de-energized.

Pack size: 1/package
In stock (0 pcs)
Estimated delivery time, if not in stock: 21 days

Operational voltage, AC
-
Operational voltage, DC
1000-3000VDC
Voltage indicator
Flashing LED indicate voltage presence, +/-/earth
Test point
High impedance protected test point 20 kOhm, +/-/earth
Voltage category
CAT III at 1000VDC, CAT IV at 600VDC
Output accuracy
10:1 voltage divider, a 1000V voltmeter shows 300V if the voltage is 3000V
Supply voltage
Self-supplied, external supply voltage not required
Installation
30,5mm knockout
Ingress protection
IP2X, IP66, IP69 according to IEC60529/UL type 4,4X,12,13
Terminations
3 wires AWG14 (2,1mm²), 2,4m long
Standard
IEC/EN 61010-2-30, CE, UL 61010-1, CSA C22.2 No94.2, UL50E
UL file nr
cUL file E311256
Parts included
Voltage ind./test point, horizontal label, protection cap
Weight, each
0,4kg
Manufacturer's part number
R-3MT-VI-3K/10-DC3-KIT-H


ChekVolt voltage indicator/test point

Increase personal safety, install ChekVolt voltage indicator/voltage test point. ChekVolt allows you to test absence of voltage with a standard voltmeter without open the enclosure door.

  • Voltage indicator and test point in one device
  • Flashing LED voltage present indication
  • High impedance protected  test points, use a standard multi-meter to verify absence of voltage
  • Ingress protection IP66
  • Installed in a 30,5mm knockout

Avoid arc flash hazards, work de-energized, perform voltage absence test with closed enclosure door.

For more information, contact one of our
PRODUCT SPECIALISTS
Product specialist
Niclas Anderberg
+46 42 386104
+46 726 006611